1. Volumetric Flow & Compression Thermodynamics (Real-Fluid EOS)
ṁ = ρ₁' · λ(Π, N) · V_disp · (n / 60) | Q₀ = ṁ · (h₁ − h₃) | P_shaft = ṁ · (h₂s − h₁') / η_is(Π, N)
Suction-gas preheat (state 1 → 1'): h₁' = h₁ + (Q_motor,in + Q_inv,in) / ṁ | Discharge enthalpy: h₂ = h₁' + (P_shaft − Q_shell) / ṁ | 1st-Law check: Q₀ + P_el = Q_cond + Q_shell + Q_ext
2. Transcritical R744 (CO₂) Optimal Gas-Cooler Pressure
p > p_crit (73.77 bar): Golden-Section optimization maximizes COP_cool(p_gc) over [75 bar, 130 bar] at fixed gas-cooler outlet T_gc using ridge-aligned Real-Fluid EOS tables.
3. DIN EN 12900:2013 & AHRI 540-2020 Polynomial Mode
Y(T_o, T_c) = Σ c_i · T_o^a · T_c^b (10-coeff) | 20-coeff adds speed terms S ∈ {Hz, rpm, rev/s}. Actual-cycle density/enthalpy correction: Q₀,act = Q₀,ref · (ρ₁,act/ρ₁,ref) · (Δh_0,act/Δh_0,ref). Zeotropic blends (R454B) evaluated at dew-point T_c per DIN EN 12900.
4. Frame-Scaled SiC MOSFET vs. Si IGBT VFD Loss Model
Q_inv = P_cond(I_rms, R_DS / V_CE0) + P_sw(I_rms, V_DC, f_sw) + P_rect(AC supply) + P_aux | External ALVC cooling routes ≤ 800 W to Heatsink/Vapor Chamber and > 800 W to Liquid Cold Plate.
5. Standards & Engineering Limits
DIN EN 12900:2013, AHRI 540-2020, ISO 10628-2, Real-Fluid EOS (IIR reference state). Built-in Reference Map is a generic technology model for preliminary sizing; paste OEM polynomial coefficients for datasheet-verified selection.
- Single-stage compression without economizer / EVI vapor injection (planned for V2).
- When Power Polynomial Basis is set to Total Electrical incl. VFD, Q_inv is separated diagnostically for cooler sizing without double-counting into P_el.
- Oil circulation enthalpy and mechanical bearing wear outside the speed envelope are not modeled; verify manufacturer oil-return and discharge limits (T₂,max).